The great source of wikipedia (wikipedia.org) helps us understand about electrical conductivity of copper and aluminium wire cables:
Electrical conductivity is a measure of how well a material transports an electric charge. This is an essential property in electrical wiring systems.
Copper has the highest electrical conductivity rating of all non-precious metals.
Aluminium has 61% of the conductivity of copper. The cross sectional area of an aluminium conductor must be 56% larger than copper for the same current carrying capability.
Electrical wiring article (original article from wikipedia.org) describes Copper and Aluminium conductors:
Copper conductors
Electrical devices often contain copper conductors because of their multiple beneficial properties, including their high electrical conductivity, tensile strength, ductility, creep resistance, corrosion resistance, thermal conductivity, coefficient of thermal expansion, solderability, resistance to electrical overloads, compatibility with electrical insulators, and ease of installation.
Despite competition from other materials, copper remains the preferred electrical conductor in nearly all categories of electrical wiring.[8][9] For example, copper is used to conduct electricity in high, medium and low voltage power networks, including power generation, power transmission, power distribution, telecommunications, electronics circuitry, data processing, instrumentation, appliances, entertainment systems, motors, transformers, heavy industrial machinery, and countless other types of electrical equipment.
Aluminium conductors
Aluminium wire was common in North American residential wiring from the late 1960s to mid-1970s due to the rising cost of copper. Because of its greater resistivity, aluminium wiring requires larger conductors than copper. For instance, instead of 14 AWG (American wire gauge) for most lighting circuits, aluminium wiring would be 12 AWG on a typical 15 ampere circuit, though local building codes may vary.
Aluminium conductors were originally indiscriminately used with wiring devices intended for copper conductors. This practice was found to cause defective connections unless the aluminium was one of a special alloy, or all devices — breakers, switches, receptacles, splice connectors, wire nuts, etc. — were specially designed for the purpose. These special designs address problems with junctions between dissimilar metals, oxidation on metal surfaces, and mechanical effects that occur as different metals expand at different rates with increases in temperature.
Unlike copper, aluminium has a tendency to cold-flow under pressure, so screw clamped connections may get loose over time. This can be mitigated by using spring-loaded connectors that apply constant pressure, applying high pressure cold joints in splices and termination fittings, and torquing the bolted connection.
Also unlike copper, aluminium forms an insulating oxide layer on the surface. This is sometimes addressed by coating aluminium wires with an antioxidant paste at joints, or by applying a mechanical termination designed to break through the oxide layer during installation.
Because of improper design and installation, some junctions to wiring devices would overheat under heavy current load, and cause fires. Revised standards for wiring devices (such as the CO/ALR "copper-aluminium-revised" designation) were developed to reduce these problems. Nonetheless, aluminium wiring for residential use has acquired a poor reputation and has fallen out of favour.
Aluminium conductors are still used for bulk power distribution and large feeder circuits, because they cost less than copper wiring, and weigh less, especially in the large sizes needed for heavy current loads. Aluminium conductors must be installed with compatible connectors.